CEM DT-5300B Digital Earth Resistance Tester
It can be used for measurements of the other low regular and liquid resistances. It can also be used for measurement of voltage AC, voltage DC and earth voltage. This instrument finds wide application for testing earthen installation in power based industries,...
Taxes included. Free shipping across India.
Key features
It can be used for measurements of the other low regular and liquid resistances. It can also be used for measurement of voltage AC, voltage DC and earth voltage. This instrument finds wide application for testing earthen installation in power based industries, telecommunication networks and electrical traction systems etc
- It is designed for measurement of the resistance of earthen used in the electrical equipment as well as for measurement of ground resistivity. It can be used for measurements of the other low regular and liquid resistances. It can also be used for measurement of voltage AC, voltage DC and earth voltage. This instrument finds wide application for testing earthen installation in power based industries, telecommunication networks and electrical traction systems etc
Specification
| Earth resistance range | 20W, 200W, 2000W |
| Display | Large LCD with dual display |
| Multimeter function Range | 200kW, 750VAC, 1000VDC |
| Sampling Rate | 2.5 times per second |
| Zero Adjustment | Automatic adjustment |
| Over Range Indicator | Number 1 of highest digit is displayed. |
| Low Battery Indication | The is displayed when the battery Voltage drop below the operating voltage |
| Power | Auto Power Off |
| Operating Temperature | 0ºC to 40ºC (32ºF to 104ºF) and Humidity below 80% RH |
| Storage Temperature | -10ºC to 60ºC (14ºF to 140ºF) and Humidity below 70% RH |
| Power source | 6×1.5V Size “AA” battery or Equivalent (DC9V) |
| Dimensions | 200(L) x 92(W) x 50(H) mm |
| Weight | Approx 700g include battery |
Accuracies are specified in the way:
±(…% of reading +…digits) at 23ºC ±5ºC, below 80% RH.
Earth resistance
| Range | Resolution | Accuracy |
| 20W | 0.01W | ±(2%+10d) |
| 200W | 0.1W | ±(2%+3d) |
| 2000W | 1W | ±(2%+3d) |
Earth voltage
| Range | Resolution | Accuracy |
| 200V | 0.1V | ±(3%+3d) |
OHMS
| Range | Resolution | Accuracy | Overload Protection |
| 200kW | 0.1kW | ±(1%+2d) | 250Vrms |
DC Voltage
| Range | Resolution | Accuracy | Input Impedance | Overload Protection |
| 1000V | 1V | ±(0.8%+3d) | 10MW | 1000Vrms |
AC Voltage
| Range | Resolution | Accuracy | Input Impedance | Overload Protection |
| 750V | 1V | ±(1.2%+10d) | 10MW | 750Vrms |
Applications
It can be used for measurements of the other low regular and liquid resistances. It can also be used for measurement of voltage AC, voltage DC and earth voltage. This instrument finds wide application for testing earthen installation in power based industries, telecommunication networks and electrical traction systems etc
Accessories
- ACCESSORIES: Batteries
- Instruction Manual
- Test Leads
- Spikes
- Cables
- Hard Carrying Case
- Test Certificate and Test Certificate
CEM DT-5300B Digital Earth Resistance Tester
Datasheets and manuals for this instrument, as PDF.